TAPE WOUND CURRENT TRANSFORMER-75 SERIES

Selection Table and Dimensions

Part Number Coding Weight Class Burden A(+/-3) B(+/-2) C(+/-0.5) D(+/-0.5) E(Ref) ID(+/-0.5) G(Ref)  H(Ref) I(Ref)  J(+/-2)
Kg VA mm mm mm mm mm mm mm mm mm mm
CT-TF-0075/05-C04-BO3-ID003-C1 0.875 1.0  5.0  105.0 45.0 85.0  110.0 80.0 35.0 20.0 50.0 35.0  70.0
CT-TF-0075/05-C04-BO3-ID004-C1 0.876 1.0 3.75 105.0 45.0 85.0 110.0 80.0 35.0 20.0 50.0  35.0  70.0

NOTE: All other Special Accuracy Classes like 0.1 -0.2-0.2s-0.5-1-3-5 and for specified Burden ranges like 2.5 – 3.75 – 5 -7.5 – 10 – 15 -20 – 30 VA and Inner diameter will be supplied based upon your request.

Design Drawing

 Technical Data
Nominal System Voltage/ NSV 0.415 KV
 Highest System Voltage / HSV 0.66 KV
 Primary Current (Ipn) 75 A
 Secondary Current (Isn) 5 or 1 A( 0.577 & 2.89 on Request)
 Frequency 50 or 60 Hz
 Accuracy Class 0.1 – 0.2 – 0.25 – 0.5 0.5S – 1 – 3 – 5
 Burden/ VA 2.5 – 3.75 – 5 – 7.5 – 10 – 15 – 30 VA
 Rated Insulation Level 0.66/3.0/ – KV
 Insulation Class A (Class ‘F’ On Request)
 ROHS Complaint ROHS (On Request)
 Standards IEC 60044-1/BS – 3938:1973/IS2705:1992
IEEE – CS7.13-1993/ANSI C57.13

Reviews

There are no reviews yet.

Be the first to review “Tape Wound Current Transformer- 75 Series”

Your email address will not be published. Required fields are marked *

    X

    MagnaTech – India, well known for its innovation, quality and commitment to customers worldwide, offers engineering design, development and innovation for various electrical components like Transformers, Inductors, Chokes etc.

    ADDRESS

    Hootagalli Industrial Area, #69/ A11, Mysuru, Karnataka 570018

    PHONE

    9845927738 / 9845642734

    Cart